 FIRE WATCH PROCEDURE

Fireproofing Safety Submittels

 FIRE WATCH PROCEDURE

Fire Watch Procedure - Intumescent Fireproofing | Reusable Template

🔥 FIRE WATCH PROCEDURE Intumescent Fireproofing

29 CFR 1926.352(e) | NFPA 51B | Solvent-Based Intumescent Coatings

1. Purpose & Scope

2. When Fire Watch is Required

⚠️ A Fire Watch is REQUIRED when:

3. Fire Watch Personnel Requirements

✓ Fire Watch Personnel MUST:
RequirementDetail / Verification
Be a dedicated person (no other duties)
Be properly trained in fire extinguisher use
Understand alarm and evacuation procedures
Have a clear line of sight to the hot work area
Remain on duty during hot work + 60 minutes after

3.1 Fire Watch Personnel Assignment

Shift / DateFire Watch NameCertification/Training DateSupervisor

4. Fire Watch Equipment

EquipmentQuantityLocationInspected / Verified
Fire Extinguisher (Class ABC or Dry Chemical)
Fire blanket
Communication device (radio/phone)
Water source (hose/bucket)
Spark-resistant tools / extinguisher hook

5. Pre-Hot Work Inspection Checklist

📋 Must be completed BEFORE any hot work begins:

6. During Hot Work Procedures

⚠️ Fire Watch Responsibilities DURING Hot Work:
  • Maintain constant visual observation of the work area
  • Watch for sparks, slag, or embers that could ignite intumescent coating
  • Monitor for solvent vapor accumulation - stop work if odors are detected
  • Keep fire extinguisher ready and accessible at all times
  • If fire occurs: sound alarm, attempt to extinguish with extinguisher, call 911
  • Communicate with welder/worker - stop work immediately if conditions become unsafe

7. Post-Hot Work Requirements (60-Minute Fire Watch)

⏱ CRITICAL - 60-MINUTE FIRE WATCH REQUIRED:
Intumescent coatings can smolder for 30-60 minutes before igniting into open flame. Fire watch MUST remain on duty for a minimum of 60 minutes after hot work stops.

8. Daily Fire Watch Log

Date Location / Area Hot Work Description Fire Watch Name Start Time End Time Post-Watch End Issues / Notes

9. Emergency Response for Fire Incidents

🔥 IN CASE OF FIRE - R.A.C.E. PROTOCOL:
📞 Emergency Contacts:

10. Fire Watch Training Record

All fire watch personnel must complete training on:
  • Fire extinguisher operation (PASS method)
  • Hazards of intumescent coatings (solvent flammability, smoldering risk)
  • Alarm and evacuation procedures
  • Communication protocols
  • 60-minute post-work monitoring requirement

11. Procedure Approval